Issues

  • Where I can find parent id to call data point api?

    We have just started testing APis. Authentication works just fine and I am able to get Tenand ID via https://api.climatixic.com/ViewNodes/ But I am missing Parent ID info. Where I can find this?

    Status: Proposed | Reported by Hidden Tue, 27 Aug 2019 13:27:36 GMT
  • Failed to access the plant

    Hi, We ran in to a problem that started on 31.7.2019. We can't see plant details or read datapoints anymore through the api. The error message we get is: "{ "errorClass": 0, "error": { "errorText": "failed to access the plant" } }" This happens for examples with requests: GET "https://api.climatixic.com/Plants/P78241262-2b2d-4bfb-99b1-5dd41c7bd587" and GET "https://api.climatixic.com/DataPoints/P68f04462-70ee-49e2-94ce-becf3a8c32d7;1!N3ASTFPG-NAOS3X" We do see those plants with requests GET "https://api.climatixic.com/ViewNodes/T9a89752d-6669-4014-bae8-227ab4553524" I can see the points when logging through the website.

    Status: Proposed | Reported by Hidden Mon, 12 Aug 2019 06:38:26 GMT
  • GET /DataPoints/Values behaviour in case of DEAD (OFFLINE) Machine

    Function: GET /DataPoints/Values observed behavior: Sends last Value of a DEAD (OFFLINE) Machine expected behavior: Sends NULL in case of a DEAD (OFFLINE) Machine Proposal: Answering policy in case of DEAD (OFFLINE) Machine should be configurable

    Status: Proposed | Reported by Hidden Wed, 22 May 2019 14:37:52 GMT
  • Adds a tenant post-API

    Response content Pragma: no-cache Access-Control-Allow-Origin: * Cache-Control: no-cache Date: Mon, 12 Jun 2017 04:15:47 GMT X-AspNet-Version: 4.0.30319 X-Powered-By: ASP.NET Content-Length: 118 Content-Type: application/json; charset=utf-8 Expires: -1 { "errorClass": 0, "error": { "errorId": "1d4b5820-b32d-4bb6-8cae-1ebac8856376", "errorText": "An unexpected error occurred" } }

    Status: Proposed | Reported by Hidden Mon, 12 Jun 2017 06:00:03 GMT
  • Cannot trigger the "Release from Manual"

    Setting the STH hot water comfort mode from Manual to Auto actually means that we have to release the datapoint DhwMod, i.e. remove the value from priority array 13. This can be done by writing value null (body={value:null}). The current API doesn't allow this and returns the error "An unexpected error occurred".

    Status: Proposed | Reported by Hidden Wed, 12 Apr 2017 11:47:37 GMT
  • Cannot write certain properties

    I can sucessfully write to datapoint SpHCmf of a STH. When I try to write to data point SpTR of the same device I get a success response from the server but the value doesn't change, i.e. I get still the old value when I read it. After doing some analysis I'm almost certain that there is a problem with the priority. The app should always write with prio 13. I added two screenshots of the priority arrays. PS. I'm using a PUT https://api.climatixic.com/DataPoints/P7322f249-95f2-4b11-a11d-bd354c812b7f;1!0020000B4000055/DataPoints/P7322f249-95f2-4b11-a11d-bd354c812b7f;1!0020000B4000055 with body {"value": 23.6}

    Status: Proposed | Reported by Hidden Wed, 12 Apr 2017 11:41:04 GMT
  • IC Web shows wrong multistate values

    The IC web page (https://www.preview.climatixic.com) shows wrong values for all multistate data points. BACnet values for multistate are 1-based and not 0-based. Example 1: The device sends value 1 for object RAQualInd (Undefined|Poor|Okay|Good) so it should show "Undefined" but the IC web page under operation shows "Poor". Example 2: The device sends value 5 for object REei (Undefined|Poor|Satisfactory|Good|Excellent) so it should show "Excellent" but the IC web page shows nothing (because it doesn't find the enum text for index 5)

    Status: Open | Reported by Hidden Mon, 10 Apr 2017 07:39:52 GMT
  • Missing Property "Relinquish Default" for SpHCmf and SpCCmf

    Some objects (like e.g. SpHCmf and SpCCmf) have also the BACnet property "Relinquish Default" (see attachment). We need this property to write the new value, i.e. it must be writable. Note that property "Present Value" is still needed as well to read the current value. In other words: We always write to "Relinquish Default" and read from "Present Value"

    Status: Resolved | Reported by Hidden Thu, 06 Apr 2017 08:56:57 GMT
  • Identify objects

    The object name is currently only available from property descr, e.g. "REei\nEnergy efficiency indication room - PresentValue" The should be a better way to identify an object. The object name is not translatable.

    Status: Proposed | Reported by Hidden Mon, 03 Apr 2017 10:31:56 GMT
  • Missing properties

    Following properties are missing: - DS1_Present_Priority (all objects) - status-flags (all objects) - resolution (analog objects) - weekly-schedule, schedule-default, DS1_Next-Value, DS1_Time-Till-Next-Value (ROpModSched and DhwSched)

    Status: Proposed | Reported by Hidden Mon, 03 Apr 2017 10:29:31 GMT